How to Set Air Shower Room Control System
1: Air shower time set:
Before the air shower room working or finished work , you can press the UP/DOWN button for change the air shower time, the rang is from 2-99second, the system display the two figure,
5 mints after you change it, the system will be save your parameter automatic.
2: The air shower room external door delay locker time. (T/T)Press the emergency button continue for 20 seconds, The control system will be come to internal parameter set program, the
Displayer screen show the TT, then you can press the up/down for set the external door delay time, the range is 0-60second, after finished the adjust , press the air shower button entrance next step, 5 seconds without any touch for the button, the system will be save the parameter and exit program.
3: Air Shower Room Internal Door Locker Delay Time: (TO)
Finished the external door, press the air shower button within 5 mints, entrance the internal door locker delay time program (TO), then press the UP/Down button for set the time, the range is 0-60second, after finished the adjust, press the air shower button entrance next step,5 seconds without any touch for the button, the system will be save the parameter and exit program.
4: The two door interlock set: (TC)
Finished the internal door set, press the air shower button within 5 mints, come into the two door interlock delay time program (TC), then press the UP/Down button for set the time, the range is 0-60second, after finished the adjust, press the air shower button entrance next step,5 seconds without any touch for the button, the system will be save the parameter and exit program.
5: Illumination time: (TL)
After the both door finished the interlocker system, press the air shower button within 5 mints, come into the two door interlock delay time program (TL), then press the UP/Down button for set the time, the range is 0-60second, after finished the adjust, press the air shower button entrance next step.5 seconds without any touch for the button, the system will be save the parameter and exit program.
6: Program system option: (TD)
After the illumination time set, press the air shower button within 5 mints, come into the two door interlock delay time program (TD), then press the UP/Down button for choose the system from 00-02, 00: standard air shower system;01: have the door but without induction system:
02: have induction but without door system. after finished the choose, press the air shower button entrance next step,5 seconds without any touch for the button, the system will be save the parameter and exit program.
7:The both door transfer set : after the program system choose, press the air shower button within 5 mints, come into the two door interlock delay time program (TN), then press the UP/Down button for choose the program from 00-01, 00:Abnormal, 01: Transfer.after finished the choose, press the air shower button entrance next step,5 seconds without any touch for the button, the system will be save the parameter and exit program.